24 / 48 V @ 10 Amps Battery Equalizer and DC Autotransformer
Application
This rugged and versatile unit is used to power a small load at 24 V from a 48 V battery,
or to power a small 48 V load from a 24 V battery. It functions both ways, producing
24 V @ 10 Amps from a 48 V input
or can be connected backwards to produce 48 V @ 5 Amps from a 24 V input.
When connected as a battery equalizer, it allows large transient 24 V loads to be taken off
the centre tap of a 48 V battery (made of 2 X 24 V batteries) without fear of upsetting the
voltage balance of the battery and destroying the 48 V battery system that would otherwise occur.
Model: EQ 24/48-10
Product similar to photo.
Features
- >95 % efficiency, typically 96 % over 20 % load
- Simple to use
- Bi-directional power flow
- Weatherproof, NEMA 4 enclosure
Electrical Specifications
|
Input low side |
Input high side |
| Input Voltage (nominal battery) V |
24V |
48V |
| Output Voltage |
48V |
24V |
| Output Current |
5A Current Limited |
10A Current Limited |
| Ripple at load |
30mV rms |
30mV rms |
| Efficiency |
>95% |
>95% |
Voltage Regulation Mode
Proportional:
This standard unit regulates the output voltage proportional to 1/2 the
input when connected 48 V input
and regulates the output to 2 X input when connected 24 V input. This characteristic,
when connected across 2 X 24 V batteries in a 48 V configuration, will keep the batteries at
equal voltages.
Fixed:
Special units are available for example EQ 24/48-10 RXX where XX is the
voltage on the 24 V side that the voltage is to be regulated to. For example, EQ 24/48-10 R27
will output 27 V @ 10 Amps to either power a 24 V load or charge a 24 V battery to 27 V.
Note: For units that require a fixed voltage at the higher voltage output, for example,
to charge a 48 V battery from a 24 V battery, use one of the Constant Voltage Regulators
Mechanical Specifications
Enclosure:
- Weatherproof, NEMA 4 enclosure
Dimensions:
- 4.5" X 2.5" X 2" nominal, resembling a junction box with feet
Weight:
Temperature Range:
- -40 deg C to 60 deg C
- It is recommended, as with all electronics, that the unit not be placed in direct sunshine
Terminations:
- 6" Flying Leads
- Red= High Input +
- Black= Common Neg. - for input and output voltage
- White= Low Input +
Wire Size:
- Red, Black, White: Power leads #12 AWG
Humidity:
Mechanical Drawing: Click here for picture
Note: In the interest of continuous product improvement, specifications subject to change without notice.
Order Model No: EQ 24/48-10
EQ 24/48-10 RXX where XX is the specified regulated voltage on the 24 V side
March 2002
|